| INPUT VOLTAGE CORRECTION
RANGE |
285-440 V AC for 3 phases;
165-255 V AC for 1 phase |
| INPUT VOLTAGE OPERATING
RANGE |
210-475 V AC for 3
phases; 120-270 V AC for 1 phase |
| OUTPUT VOLTAGE |
380 V AC RMS ± 1% (3
phases), 220 V AC RMS ± 1% (1 phase) |
| OPERATING FREQUENCY |
50 Hz ± 5 % |
| OVERLOADING |
10 seconds 500% under
load |
| CORRECTION (CONTROL)
SPEED |
~ 200 Volt / Second |
| RECOVERY TIME |
~ 500 msec. (at change
between 165 V AC - 255 V AC) |
| TOTAL OUTPUT |
> 98% (under full
load) |
| OPERATING TECHNIQUE |
RISC microprocessor
controlled full automatic servo control |
| DISPLAY AND BUTTONS |
True RMS digital voltmeter,
button scanning with microprocessor, audio alarm reset
button |
| ALARM MESSAGES |
Network high/low, output
failure and overload LED alarms |
| MONITORING THE MEASURED
VALUES |
Output, network voltage
and load percentage at 3 separate windows |
| OUTPUT TOLERANCE ADJUSTMENT |
DIP SWITCH can be selected
as 1,5%, 2,5%, 3,5% and 5% |
| OUTPUT DELAYED TIME
ADJUSTMENT |
DIP SWITCH can be selected
as 1s, 2.5s, 5s and 10s |
| OUTPUT UPPER LIMIT
CUT-OFF ADJUSTMENT |
DIP SWITCH can be selected
as 240V, 245 V, 255 V and 265 V. |
| OUTPUT LOWER LIMIT
CUT-OFF ADJUSTMENT |
DIP SWITCH can be selected
as 170 V, 180 V, 190 V and 200 V. |
| OUTPUT PROTECTION |
Short circuiting, over-current
electronic protection and load protection by switching
on the circuit by contactor at overvoltage higher
than the set value |
| NETWORK INPUT PROTECTION |
Over-current thermal fuse and instant
over-voltage protection |
| MECHANIC BY-PASS |
Manual controlled "Network-Voltage"
selector PAKO SWITCH |
| OPERATING TEMPERATURE |
0
C° / + 40 C° |
| RELATIVE MOISTURE |
Maximum 90% DIN (40040) |
| OPERATING HEIGHT |
Maximum 2000 meters |
| ACOUSTIC LEVEL |
Less than 50 dB |
| NETWORK INPUT CONNECTION |
TTR cable with plug socket (5 kVA<);
O 16 mm Ray Clements (5 kVA>) |
| REGULATOR OUTPUT CONNECTION |
Panel-type plug w/cover (5 kVA<); o
16 mm Ray Clements (5 kVA>) |
| PROTECTION AGAINST
SUDDEN VOLTAGE SHOCK |
IEEE 587 (4500 A, 100 JOULES) |
| ELECTRIC INTERFERENCE
SUPPRESSOR |
ECC Part 15 Class B, EMI - RFI filter |